Q89461: LAN Man 2.1 Test Summary (American Power Back-UPS 900)

Article: Q89461
Product(s): Microsoft LAN Manager
Version(s): 
Operating System(s): 
Keyword(s): 
Last Modified: 30-JUL-2001

SUMMARY
=======

The following are the test results for the American Power Conversion Back-UPS
900 uninterruptable power supply (UPS). The test was conducted as part of the
Microsoft Compatibility Lab (MCL) peripheral test for LAN Manager version 2.1:

MORE INFORMATION
================

Company
-------

American Power Conversion
132 Fairgrounds Rd.
West Kingston RI 02892
(800) 800-4272

Date Tested
-----------

5/26/92

Uninterruptable Power Supply Data
---------------------------------

Model:                          Back-UPS 900
Serial number:                  W920501017
Supplied cable part number:     940-0020A
Vendor supplied software:       N/A
Software part number:           N/A

UPS Switch Settings
-------------------

Switch Number       Setting
-------------       -------

    1               OFF
    2               OFF
    3               OFF
    4               OFF

The switch settings used are also factory defaults.

Testing Environment
-------------------

Operating system      OS/2 1.3
Network               LAN Manager 2.1
Test platforms        486/33 16 MB RAM
Bus specification     EISA
Network topology      Ethernet

LANMAN.INI [UPS] Settings
-------------------------

BatteryTime          60
CmdFile             N/A
MessDelay             2
MessTime            300
Recharge            100
Signals             111
VoltLevels          111

Final Test Results
------------------

Test Focus                          Pass     Anomalies and/or Workarounds
----------                          ----     ----------------------------

Installation                         Yes
Fully chargeable                     Yes
Power lost signal                    Yes
Power restored signal                Yes
Low battery signal to server         Yes
Shut down server                     Yes
Server boots when power restored     Yes
Sustains server power for 5 minutes  Yes

Additional query words: certification 2.1 2.10

======================================================================
Keywords          :  

=============================================================================

THE INFORMATION PROVIDED IN THE MICROSOFT KNOWLEDGE BASE IS PROVIDED "AS IS" WITHOUT WARRANTY OF ANY KIND. MICROSOFT DISCLAIMS ALL WARRANTIES, EITHER EXPRESS OR IMPLIED, INCLUDING THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. IN NO EVENT SHALL MICROSOFT CORPORATION OR ITS SUPPLIERS BE LIABLE FOR ANY DAMAGES WHATSOEVER INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF MICROSOFT CORPORATION OR ITS SUPPLIERS HAVE BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES SO THE FOREGOING LIMITATION MAY NOT APPLY.